Abstract

The purpose of this study is to find the infiltration of detached houses, for energy consumption analyses. The pressurization and depressurization method is used to determine infiltration. Blower door tests are expressed in terms of ACH 50, which stands for the hourly air change rate at 50 Pa of fan pressure. The ACH 50 of existing Detached Houses ranges from 5 to 50. Air infiltration is related to construction year and accuracy, maintenance conditions, and so on. When estimating the infiltration of random detached houses, the year used can be the base value of the infiltration rate from 0.25 to 2.0 times/h. The maintenance conditions, construction accuracy and repair affect the air infiltration 0 to 0.5 times/h, 0 to 0.3 times/h, 0 to 1 times/h, respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.