Abstract

Chilled Beam system is the kind of water-air system which reduces the conveyance energy for air conditioning as well as allows efficient installation and comfortable indoor environment, and has been increasingly popular mainly in Europe. To effectively install such Chilled Beam system domestically, it is necessary to develop the product considering domestic climatic condition and the requirements for air conditioning system, and particularly the way to deal with condensation during operation of cooling system in summer shall be provided. In this study, the optimal design on induction structure of Chilled Beam unit was carried out through a numerical method, and the performance test for the prototype of unit was conducted in a real-scale experiment facilities of Chilled Beam unit. While the flowrate of 1st air is 101.3 CMH, the pressure in pressure chamber is 158.7 Pa and the cooling capacities of 1st air side and 2nd air side are 498.1 W and 709.5 W respectively.