Abstract

This paper dealt with the measurement and analysis of electromagnetic waves radiated from a partial discharge (PD) source in insulation oil to apply condition monitoring of oil-immersed transformers. Two types of narrow-band monopole antennas with the resonant frequency of a 500 MHz and a 1 GHz were designed and fabricated. Also, a needle-plane electrode system was manufactured to simulate PDs and the curvature radius of the needle is 10 <TEX>${\mu}m$</TEX> and the diameter of the plane is 60 mm. Electromagnetic wave was measured by the PD measurement system with the monopole antennas. Detection sensitivity of the fabricated antenna was compared for the same PD magnitude; 620 <TEX>$mV_{peak}$</TEX> for the 500 MHz antenna and 960 <TEX>$mV_{peak}$</TEX> for the 1 GHz antenna to the PD magnitude of 74 pC. Consequently, the 1 GHz monopole antenna is more effective to detect PDs in oil-immersed transformers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.