Abstract

Fire protection (sprinkler) piping system is an essential element for the energy supply and for the protection against the seismic-induced fire during and after an earthquake. The primary objective of this study was to understand the seismic performance of complex two-story piping system installed in a low-rise building subjected to bi-directional and three-directional earthquakes. The result of current study revealed that the displacement of the piping system in accordance with floor level was significantly different due to acceleration-sensitivity but the effect of the piping system due to the vertical direction earthquake was not significant.