Abstract

In this study, we investigated the effects of hot water on the aging of URD power cables due to the hot water ingress to power distribution lines. Hot water contacted and non-contacted cables extracted from 2 distribution lines were characterized by the measurement of oxidation induction time(OIT) and chemical structure. In OIT measurement, hot water contacted cables showed the shorter OIT than non-contacted ones. Especially, hot water contacted insulation layer near insulation shield showed the shortest OIT. In chemical structure analysis, the antioxidant content was decreased and the acid concentration was increased by hot water ingress. From this results, it can be concluded that the hot water ingress to power cable may be accelerate the aging by means of antioxidant consumption.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.