Abstract
The surface of the cooling coil becomes dry, wet or partially wet depending on the operating condition. Thus, a proper design of the cooling coil should include a heat transfer analysis on dry, wet or partially wet surfaces. In this study, an elementary model, which analyzes the cooling on an elementaty basis, is proposed. Comparison of the predictions of the model with experimental data of the cooling coil revealed that heat transfer rates were predicted within 10.1%, airside pressure drop within 11.1% and sensible heat ratio within 5.7%. The model was used to investigate the effect of water circuitory on cooling coil performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korea Academia-Industrial cooperation Society
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.