Abstract

The heat transfer performance and pressure drop characteristics of brazed-plate heat exchangers with 20 and 30 plates were experimentally measured and analyzed in this study. The mass flow rates of the heat exchangers with 20 and 30 plates were fixed at 0.6 and 0.9 kg/s for the low temperature side, respectively. The mass flow rate for the high temperature side was controlled from 0.2 kg/s to 1.2 kg/s. The inlet temperatures for the high and low temperature sides were <TEX>$10^{\circ}C$</TEX> and <TEX>$7^{\circ}C$</TEX>, respectively. The heat transfer characteristics were not influenced by the number of plates. The pressure drop at the heat exchanger with 30 plates was slightly higher than that with 20 plates. The values calculated from the correlations based on gasket plate heat exchangers were compared with the experimental results. It was found that the predicted Nusselt numbers for the gasket plate heat exchangers were about 5% to 20% lower than the measured Nusselt numbers for the brazed plate heat exchangers. However, a pressure drop comparison showed that the calculated pressure drops at the gasket plate heat exchangers were less than half of the measured pressure drops at the brazed plate heat exchangers.