Abstract

In this study, real fire tests have been performed for the fire behavior and temperature analysis of the compartment. The size of Mock-up experiments were 3 m length, 3.2 m wide, 2.5 m height m. The BFD curve method of C.R. Barnett is adopted to study a empirical model for fire compartment temperatures. The fire load was with office combustible supplies including access floors. The temperatures in the Mock-up compartment were measured using two different locations of thermocouple trees. These conclusions and experiment data obtained in this paper could be helpful in reference for the fire simulation, fire hazard assessment and fire protection design (including PBD). Based on experimental data, BFD curve and mathematical models need to be discussed to predict temperature curve in flashover and fire spread in the compartment. Also, this empirical model study needs more test to verify and optimize.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.