Abstract
Malfunction and nuisance tripping of molded case circuit breaker(MCCB) caused by harmonic currents have been reported. But no data is available on the behavior of MCCB under harmonic currents. This paper tested the effects of harmonic currents on four common types of MCCB(thermal, thermal magnetic, magnetic and electronic types). Results of experiment detected no nuisance tripping with any of the breakers tested under test currents, included harmonic current, below rated currents. Additionally it was found that varying harmonic loading conditions did not affect manufacturer specified trip times for thermal only and thermal magnetic circuit breakers. However, under overloaded conditions, trip times of the magnetic only circuit breakers were gradually slowed according to increasing of harmonic currents, and it could cause hazardous overheating of cables. So, the use of magnetic only circuit breakers in the place harmonic currents we serious must be avoided.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.