The paper presents the results of theoretical analysis and mathematical processing of experimental studies of the insulation state of individual elements of the same type of sections of 0.4 kV electric networks in underground workings conducted at the mining and processing mines at heights of workings up to 1000 m above sea level. The studies were carried out according to a single method in order to identify the effect of highlands on the insulation state of individual elements of 0.4 kV networks. It is recommended to complete scraper winches, fans and other mechanisms of high-altitude mines with organosilicon-insulated engines or with front coatings filled with top coat varnishes similar to excavator engines. A similar situation is noted with the launcher. More than 50 % of all the equipment of high-altitude mines have an active insulation resistance of less than 20 mOhm. A higher asymmetry of the total and active insulation resistance of launchers is noted. It is recommended to use silica gel to reduce air humidity inside the shells of the launcher...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.