Abstract

The most important factors relating to the indoor air environment are temperature, airflow, humidity, and contaminant concentration. A sensitivity analysis of indoor environment factors was carried out to grasp influences along with changes of atmospheric conditions. An integrated multizone model was used to predict these sensitivities. This model was applied to an apartment with six zones. Airflow rates are influenced very seriously by changes of wind direct or wind velocity, but are influenced very slightly by changes of outdoor air temperature and are not influenced at all by changes of outdoor air humidity or contaminant concentration. Indoor air temperatures are influenced very directly by changes of outdoor air temperature, but are influenced very slightly by wind direction or wind velocity and are not influenced at all by changes of outdoor air humidity or contaminant concentration. Indoor air humidities are influenced very directly by changes of outdoor air humidity, but are not influenced at all by changes of outdoor air contaminant concentration and have little or no influence by changes of wind direction, wind velocity, or outdoor air temperature. Indoor air contaminant concentrations are influenced very seriously by changes of wind direct or wind velocity, but are influenced somewhat by changes of outdoor air contaminant concentration and are influenced very slightly by changes of outdoor air temperature and are not influenced at all by changes of outdoor air humidity.