Abstract

Multiple ground rods are commonly used to obtain the low ground impedance, but they will not reduce the ground impedance unless the spacings between the ground rods are sufficient. This paper presents the experimental results of frequency-dependent resultant ground impedance of two ground rods in parallel. The resultant ground impedance of two ground rods in parallel were measured as functions of the spacing and length of ground rods and the frequency of test currents and were discussed based on the potential interferences. As a consequence, the frequency-dependent ground impedance of single ground rod and two combined ground rods give capacitive. It was found that the effect of potential interference on the ground impedance is directly associated with the frequency-dependent ground impedance and is strong in low frequency. Also, in order to reduce the increasing rate of resultant ground impedance of two ground rods due to potential interference to within 10(%), two ground rods in parallel will be placed over one rod length apart.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.