Abstract
This paper presents measurement results of transient impedance for small-sized ground electrodes in a discharge region of soil. For a realistic analysis of ionization characteristics near the ground electrode, three types of ground rod installed outdoors and high voltage impulse generator were used for injecting test current. From the analysis of response voltage and current flowing ground electrode to earth, it is verified that the ionization near the ground electrode contributes to reduction of ground impedance and limits the ground potential rise effectively in high resistivity soil. As a threshold electric field density for ionization is small in low resistivity soil, the shape of ground electrode rarely contributes to the transient impedance. And, from the experiment result with shape of ground electrode, the rod with needles is more effective to reduce the transient impedance than the plate electrode in the voltage range including with ionization regions of soil.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.