Abstract

This paper presents The performance analysis of inverter control type-industrial cooler with respect to refrigeration load and outdoor temperature. Aside from materials about simulations and foundation data regarding inverter control compressors, currently, data about commercial coolers with inverter control still lack information for performance comparison. Thus, in this paper, the experiments are done to see characteristics of condensation capacity, evaporation capacity, compressor power and COP with respect to outdoor temperature and load by using a commercial inverter control cooler model. As a result, COP difference of the inverter control cooler with respect to load is 30% at the outdoor temperature of <TEX>$35^{\circ}C$</TEX>, 29% at the outdoor temperature of <TEX>$30^{\circ}C$</TEX>, 34% at <TEX>$25^{\circ}C$</TEX>, respectively.