Abstract

The electrical safety management act stipulates the implementation of a safety class system for inspection that overcomes the pass-fail system to raise the class of safety management for electrical facilities. Because the conventional safety class system only applies to scheduled outage inspection of electrical facilities, difficulties arise in implementing uninterruptible inspection of electrical facilities. This paper proposes the method for applying a safety class system that utilizes the results of the uninterruptible inspection. To achieve this, the proposed method recalculates the weight factor based on the conventional inspection items and constructs safety class assessment items for the application of uninterruptible inspection results. The performance of the proposed method was investigated using periodic inspection data in real site. The results of the case study indicate that the proposed method can derive the safety class by performing an uninterruptible inspection compared to a safety class based interruptible inspection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.