Abstract

This study attempted to find an alternative method for fine dust control in the pre-exiting facilities of metro-subway stations. A new double-layer design was proposed for the MVAC (mechanical ventilation and air control) system. Several filter lay-outs were combined a pre-filter with electret filter (EF), electret bundle filter (EBF), or electret pleated filter (EPF), and were then examined focusing on the collection efficiency of particulate matters and pressure drop across the filter layers. The experimental results from the lab and field tests showed the best collection efficiency with EPF, which achieved 85% for and 55% for . It was also found from the long term field test that the new filter lay-out could provide quite consistent dust level particularly in underground platform regardless of external condition.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.