Abstract

Heat pump systems are recognized to be heating and cooing systems. In this study, to check the practical application possibility of heat pump systems as low temperature storage systems and get basic data, apples of a long term storage items were stored and performance of low temperature storage and quality changes of apples were evaluated. Cooling coefficient of performance of the system was from 1.1 to 1.3. Although ambient air temperature varied widely from <TEX>$-13^{\circ}C$</TEX> to <TEX>$29.6^{\circ}C$</TEX> during low temperature storage period from January to June, the average temperature of low temperature storage chamber was <TEX>$1.1^{\circ}C$</TEX> at setting temperature of <TEX>$1.5^{\circ}C$</TEX>. Sucrose of apples stored by the heat pump decreased from initial sucrose of 15.4% (Brix number) to final sucrose of 14.3%. Weight loss ratio of apples was 9.7% and internal and external view of apples after low temperature storage were very satisfactory with the naked eye.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.