Abstract
This study deals with the design of a bi-directional damper using a tuned liquid damper(TLD) and a tuned liquid column damper(TLCD) for a SDOF building. Two dampers are usually needed to reduce wind-induced responses of tall buildings since they are along and across wind ones. The proposed damper has the advantage of controlling both responses with a single damper. The damper used in this study behaves as both a TLCD in a specific translational direction and a TLD in the other orthogonal direction. This paper presents experimental verification to confirm its control performance. First, shaking table test is carried out to investigate reducing responses by the damper. Control performance of the damper is expressed by the transfer function from shaking table accelerations to SDOF building ones. Testing results show that the damper reduced bi-directional responses of a SDOF building. Also, it reduced torsion responses.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Transactions of the Korean Society for Noise and Vibration Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.