Abstract

Domestic low-voltage electrical equipments have an environment prone to ground potential interference, due to the characteristics of grounding system. This ground potential interference affects electrical equipments and communication facilities, and amplify the error of ground resistance measurement. It is desirable to find and eliminate the root cause of ground potential interference, however it is difficult to remove that in an environment such as in a dense urban area or an area adjacent to the transmission line. In this paper, the pattern of the potential interference voltage and the effect on the conventional ground resistance measurement are analyzed based on the actual field measurement cases of the ground potential interference, and propose a ground resistance measurement method that reflects the characteristics of ground potential interference.