I f a part of the poor solution from the absorber outlet is recirculated to the absorber inlet, the solution temperature at the solution spray pump can be reduced, and the solution flow rate in the absorber is increased. We have performed the experiments on the influences of the absorption chiller performance according to the ratio of the recirculation, defined as the ratio of the recirculation flow rate to the total solution flow rate at the absorber outlet. As increasing the ratio of the recirculation, the absorption capacity of the solution can be deteriorated. On the other hand, due to the increasing flow rate, the heat transfer rate can be enhanced. As a result, the performance of the absorber and the cooling capacity of the absorption chiller have nothing to do with the recirculation ratio, and the lifetime of the spray pump will be maintained.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.