Abstract

The people who are in the noise factory are difficult to hear and recognize about fire and to evacuate quickly when a fire occurs. This study was conducted to analyze workplace's background noise of 31 factories in Incheon and to know the workplace noise level comparing to fire alarm sound level. The measured average noise level was 96.8dB(A). Noise level of measured result was exceeded as 6.8dB(A) comparing to NFSC (National Fire Safety Code) noise level of 90dB. NFPA suggests that when background noise exceeds 85dB or more than that, other methods should be considered to know alarm sound. Also fire alarm sound should exceed more than 15dB(A) comparing to background noise level. Therefore it was concluded that the design of the fire alarm systems should not be applied to the workplace without considering background noise and it needs to be improved with regulations and the systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.