Abstract
An increase in a distributed generation (DG) causes an excessive voltage problem unless there is proper complement action. The direct voltage control, however, might cause control issues of hunting between adjacent DGs. This paper proposes an indirect voltage control method based on a non-linear P-Q droop curve that is estimated using the Kalman-filter algorithm. For effective estimation, PQV curved surface is estimated, from which the P-Q droop curve is extracted with the condition of zero voltage variation. The effectiveness is verified based on a practical microgrid model composed of real island power system data. For the simulation-based verification, power system computer aided design/electromagnetic transient including DC (PSCAD/EMTDCTM) is used.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The transactions of The Korean Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.