Abstract

One major breakthrough in the field of heating, ventilation and air conditioning has been the development of heat pumps. Heat pump systems offer economic alternatives for recovering heat from different sources for use in various industrial, commercial and residential applications. In recent years, the heat pump has been tipped to have a very good potential for hot water production. This paper investigated the performance of a vapor injection heat pump with the variation of sub-cooler capacity at heating mode. The heating capacity of the vapor injection heat pump slightly increased with an increment of sub-cooler capacity, while COP didn't increase continuously. The 20% capacity of sub-cooler comparing with system capacity could be used as a standard to select sub-cooler capacity.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call