C로 증가할수록 냉방용량은 19.1 kW에서 20.5 kW로 7.3% 증가했으나 냉방성능(COP)는 4.67에서 5.1로 7.0%감소하였다. Abstract: The objective of this study is to investigate the cooling performance of an air-conditioning system for a special purpose vehicle under tropical and severe weather conditions. In order to evaluate and compare the cooling performances, the dual refrigeration cycle using R-134a was tested on a special purpose vehicle with various refrigerant charge amounts and indoor temperatures. The cycle was tested considering indoor cooling speed and compression ratio (discharge pressure), and was optimized at the refrigerant charge amount of 1.5 kg and outdoor temperature of 40.0 °C. The time to reach indoor temperature of 15.0 °C increased by 86.5% and 38.1%, at the indoor temperatures from 25.0 °C to 32.5 °C and from 32.5 °C to 40.0 °C, respectively. In addition, with the increase in indoor temperature from 25.0 °C to 40.0 °C, the cooling capacity increased by 7.3%, from 19.1 kW to 20.5 kW, but decreased by 7.0% from 4.67 to 5.1.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.