Abstract
The paper presents the results of studying the effect of wire sagging on the charging capacity of an overhead power line. A refined mathematical model of the overhead line charging capacity is obtained. The results of the study of the error of neglect of wire sagging for typical structures of overhead power lines with voltage from 35 to 750 kV with the arrangement of wires in 2-3 tiers and horizontal arrangement are presented. The influence of changes in the wire sagging boom on the value of the power line charging capacity due to changes in the operating temperature of the wire and due to ice deposits is investigated. It is shown that for 750 kV power lines, such a change can reach 1-1.5%, which, in combination with the long length of the main power lines, can cause a change in the balance of reactive power in the line itself and in adjacent power systems. The possibility of monitoring the wire sagging boom in a run is investigated and the requirements for the accuracy of such measurements are determined. Bibl. 14, fig. 3, table.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Praci Institutu elektrodinamiki Nacionalanoi akademii nauk Ukraini
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.