Abstract
The method of analytical thermal calculation of dry transformers with cylindrical conductors with cast insulation and foil windings is presented. The surface and volume averaged temperatures of the magnetic system core and the wind-ings are determined from the one-dimensional non-linear substitute thermal circuit of the transformer. To clarify the temperature distribution across the cross-section of the anisotropic foil winding, the solution of the boundary value problem in the form of a two-dimensional Poisson equation with heat transfer coefficients calculated from the substitute scheme is used. Calculation example of a dry transformer with a capacity of 2500 kVA is given. Numerical CFD model-ing was performed to verify the calculation results. Bibl. 10, fig. 9, tab. 3.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Praci Institutu elektrodinamiki Nacionalanoi akademii nauk Ukraini
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.