Abstract

This paper presents an experimental study on the optimal settings for the selected DC fault relay (50F) to improve the operating performance for the high-speed circuit breaker on DC feeding system which ensure safety within rolling stock maintenance depot. In this study, current supplied to overhead contact wire was calculated on 1 ms interval to analyze the correction values of DC fault selective relay for the operation of current supply cutout. Particularly, standards for the accurate detection of accidents between an electric railway vehicle and the electric power facilities are shown by investigating the optimal correction values for detection of fault current, and the results indicated that it takes about 213 ms for the DC fault selective relay(50F) to fully open. In the future, the correction values of DC fault selective relay suggested in this paper will be used as the reference values of protective relay for the safe operation of DC electric railroad system such as urban railway.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call