Abstract
In this study, wet surface heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. Both j and f factor decreased as number of tube row increased. Compound enhanced fin samples yielded higher j and f factors than louver fin samples. For one row, j and f factors of compound enhanced fin samples were 11% and 43% higher than those of louver fin samples. For two row, those were 8% and 50%, and for three row, those were 17% and 53%. Heat transfer capacities at the same pressure drop of the compound enhanced fin samples were 2.0% for one row, 3.1% for two row and 8.4% for three row larger than those of louver fin samples, Data were compared with predictions of existing louver fin correlations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korea Academia-Industrial cooperation Society
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.