Abstract

During the operation of 0.4 kV electric networks, asymmetry of currents and voltages is unavoidable. As is known, unbalanced operation of 0.4 kV networks is stemming from nonuniform distribution of loads between the phases. This results in that a fundamental frequency zero-sequence current will flow through the neutral conductor in a four-wire three-phase electric network. On the other hand, during balanced operation of a four-wire electric network containing loads with a nonlinear volt-ampere characteristic, higher harmonic currents multiple to three are summed in the neutral conductor. Therefore, it is of relevance to analyze unbalanced operating conditions of a four-wire electric network containing loads with a nonlinear volt-ampere characteristic. The article presents the characteristics of a municipal load for analyzing unbalanced/nonsinusoidal conditions of its operation. For carrying out full-valued assessment of unbalanced operating conditions of a four-wire electric network, a simulation model of a 0.4 kV network section containing a nonsinusoidal load is developed. It is shown that during unbalanced operation of an electric network containing electric loads with a nonlinear volt-ampere characteristic it is recommended to take into account zero-sequence current higher harmonic components that are not multiple to three. An algorithm for calculating the neutral conductor current harmonic component for determining the cable temperature rating is developed.