Abstract

The article presents the results of full-scale and computational studies of reinforced concrete structures of the shield wall of the PSPP building and the fl oating bulkhead of the dry dock, which are important structures, on the condition of which the construction and operation of the pumped-storage power plant and the dry dock depend. Based on the survey data, the nature of crack formation in the shield wall of the PSPP building and in the front wall of the floating bulkhead (facing towards the dry dock) was established. The acting loads and causes of crack formation were determined. The actual stresses in the armature were determined by the «valve unloading» method. Fines were cut down in concrete, the studied rod armature was bared, on which deformometers were installed and zero readings were taken. Calculation studies of the VAT of reinforced concrete structures of the shield wall of the PSPP building and the dry dock floating dam were carried out on the basis of spatial finite element models, including the structure and the base. The measures to reinforce the shield wall of the PSPP building with carbon fabrics were developed and practically implemented; the measures to strengthen the walls of the floating bulkhead were proposed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.