Abstract
Tall and slender substation equipment is prone to failure under seismic excitations. The consequences of such failure can be devastating and lead to weeks or months of lost power. The IEEE Std 693-2005 ensures that all substation equipment installed in high seismic areas are designed to withstand earthquakes of a severity related to that area. There are numerous ways to increase the seismic strength of substation equipment and this paper will discuss doing so by base isolation, specifically using wire rope isolators (WRIs). It is the purpose of this paper to present a case study in which the Socitec Group provided a WRI base isolation design for a high voltage surge arrester. The simulation results show that the moment at the base of the surge arrester was reduced by 55% when using the Socitec designed WRI base isolation system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.