Abstract

Experiments are described which indicate the effect upon pulse breakdown voltage of high current arcing between copper electrodes in vacuum. Our results indicate a moderate degradation of breakdown voltage occurs when the electrode surfaces have been arced at currents exceeding 5000 A peak. This change is probably associated with the melting and erosion of the contacts by the arc. The degradation at the arc anode and the arc cathode appear to be about equal for all currents up to 45 kA peak.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.