Abstract

There is growing awareness concerning the variety of VOCs as well as their level in the indoor air. Measurements of VOCs were carried out in both the indoor and the outdoor air of six office buildings in Greece together with the measurements of other physical and chemical parameters. The experimental results showed that the toxic VOC (TVOC) concentrations in 65% of the rooms were higher than the recommended level of 200 μg.m-3 and that the concentrations of TVOCs in the outdoor air were lower than the concentra tions in the indoor air in all the buildings examined. More than 60 compounds were identified from the TVOCs in each building among which the aromatic and aliphatic compounds were the most abundant. Although a number of oth er compounds were found, including terpenes, ketones, alcohols, aldehydes, esters and halogenated compounds, most of them did not exceed the level of 20 μg.m -3 in most of the rooms.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.