Abstract

Surface flashover characteristics of solid spacers in a rod-plane configuration have been investigated in SF/sub 6/, at pressures to 400 kPa, for switching impulse voltages to determine the effect of spacer, spacer materials and polarity of applied impulses. The effect of spacer material on the flashover voltage is not significant. For negative polarity impulses, the influence of the spacer is also insignificant. But for positive polarity impulses, at pressures <200 kPa, the spacer efficiency becomes >1.0. On the other hand, at pressures >200 kPa, the presence of the spacer drastically reduces the flashover voltage of the system. At about atmospheric pressure also, the spacer efficiency in air has been found to be >1.0, with the same electrode geometry.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.