Abstract

Laboratory and field studies of five Texas distribution systems suggest that chlorite ion has significant potential for controlling nitrification in chloraminated water.Controlling nitrification is essential if chloramines are to be a viable alternative disinfectant scheme for distribution systems in all types of environments. This article reviews problems associated with nitrification and presents laboratory and field evidence for using the chlorite ion (ClO2–) to control nitrification in distribution systems. Laboratory experiments in this study showed that even low dosages of ClO2– (0.05 mg/L) can inactivate 3–4 logs of ammonia‐oxidizing bacteria (AOB) over several hours. Higher concentrations of ClO2– inactivate all of the AOB in as little as 30 minutes. Field investigations at five Texas water utilities showed that the presence of ClO2– in the distribution systems resulted in less loss of chloramines and ammonia–nitrogen and thus less nitrification than in those systems in which ClO2– was not present. The ease of use of ClO2– is compared with other, more traditional nitrification control measures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.