Abstract

The basic design of the high-voltage thyristor valve developed for the Vyborg converter substation is described. The parameters of the design impulse voltage across the valve and the model of the converter bridge valve assembly are justified. It is established that when subject to a design lightning impulse voltage, the designed valve ensures safe operation in terms of the voltage amplitude and voltage rise rate in the thyristors. It is shown that the difference between the detailed and simplified model does not exceed 3%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.