Abstract
In this paper, the unsteady state calculational model is proposed for the thermal stratification analysis in the feedwater line of the PWR plant. By defining dimensionless parameters in the two-dimensional polar coordinate system and applying SIMPLE algorithm, the temperature and flow profiles due to the thermal stratification are obtained. Base on the fact that the most significant condition occurs when the fluid temperature difference between the piping ends reaches as high as 166.deg. C, the present result shows that max. Dimensionless temperature difference of 0.6 (about l00.deg. C) obtained between hot and cold sections of pipe wall at dimensionless time 47.0.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Transactions of The Korean Society of Mechanical Engineers B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.