Abstract
This paper presents local heat transfer results obtained during the condensation of Isceon 59, R407C and R404A in a smooth horizontal tube. The results have been compared with existing correlations for condensation heat transfer to assess the validity of these models for refrigerant mixtures. Two correlations (Dobson MK, Chato JC. Condensation in smooth horizontal tubes. Journal of Heat Transfer, Transactions of ASME 1998; 120: 193–213, Shah MM. A general correlation for heat transfer during film condensation inside pipes. Int J Heat & Mass Transfer 1979; 22: 547–56) have been considered because they deal with refrigerant blends and their range of applicability suited the experimental test conditions. The Dobson and Chato correlation provided the best prediction for these refrigerant mixtures. The Shah correlation fitted the measurements of the local heat transfer coefficients well and seem to cope well with refrigerant mixtures.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.