Abstract

Reliable operation of multichannel power electronic converters in a large pumped storage power plant (PSPP) is a main concern among policymakers and/or hydropower project developers. This paper aims to design a two-stage protection circuit operation strategy for a large-rated doubly fed induction machine (DFIM) employed for variable-speed PSPPs. This paper initially studies the dynamic behavior of DFIM under symmetrical short-circuit faults in both the 400-kV power system and at stator terminal of the generating unit. Based on the fault analysis, a two-stage protection circuit (dc-link braking chopper circuit and crowbar protection circuit) operation strategy is designed in consideration of practical limitations. The designed operation strategy ensures the continuous operation of large-rated DFIM under marginal grid disturbances. To investigate the effective operation of a two-stage protection circuit, a 250-MW DFIM with multichannel power converters is implemented in MATLAB/Simulink tool. An experimental test is carried in a 2.2-kW DFIM laboratory prototype.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.