Abstract

Aiming at the uncertain optimization problem of AC/DC hybrid distribution network under the coordination of source, grid load and storage, an AC/DC hybrid distribution network operation scheme based on two stage affinely adjustable robust optimization was proposed in this paper. Firstly, the controllable model of distribution generation (DG), the battery energy storage model with cycle life degradation and the ZIP load model were considered, and the optimization model of AC/DC hybrid distribution network economic operation was constructed. Then the ellipsoid set was used to describe the uncertainty of DG output, and the linear decision-making mechanism of decision variables and uncertainty variables of DG output in the optimization model was formed by combining linear affine strategy, Finally, the robust optimization model of AC/DC hybrid distribution network was transformed into a deterministic mixed integer second-order cone programming model by dual transformation. The effectiveness and advantages of the affinely adjustable robust optimization method proposed in this paper were compared and verified in the two modified IEEE bus system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.