Abstract

In this study, the feasibility of forward osmosis (FO) hybridized with membrane distillation (MD) was systematically investigated for treating flue gas desulfurization (FGD) wastewater. FO experiments were conducted using raw FGD wastewater obtained from a coal-fired power plant in Korea. Severe membrane fouling in FO was observed since FGD wastewater contained various components (i.e., particles, colloids, organics, and ions). The combined fouling layer by particulates and scales was identified via scanning electron microscope (SEM), energy dispersive X-ray (EDX) and X-ray diffraction (XRD). Therefore, fouling control strategies were suggested and evaluated. Microfiltration (MF) pre-treatment was effective in removing particulates and mitigating the initial fouling. Antiscalant-blended draw solution (DS) could inhibit the formation of membrane scaling. With such fouling control schemes, FO achieved the highest recovery rate compared to other desalting processes (i.e., RO and MD), suggesting that FO is suitable for treating wastewater with high fouling potential and high TDS. Finally, the diluted DS was recovered by MD. MD could re-concentrate the diluted DS up to 50% recovery rate with no significant flux decline. Rapid flux decline was then observed due to membrane scaling. Thus, appropriate antiscalants in DS should be considered to inhibit scaling formation in FO and MD simultaneously.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.