Abstract

The space charges around a HVDC transmission line may not only lead to electromagnetic environmental problems but also affect the occurrence of impulse corona and then the transient overvoltage propagation. This paper derives the equations governing the transient overvoltage propagation along a HVDC transmission line when there is either space charges surrounding the line or impulse corona. In contrast to conventional transmission line equations, the proposed equations adopted the dynamic capacitance C ′ and conductance G to characterize the corona discharge in all cases, which can be obtained by a time-domain finite element method. A finite-difference time-domain method is introduced to solve the nonlinear transmission line equations. The validity of the proposed approach is verified by comparison with the lightning overvoltage waveforms measured in a literature. The transient overvoltage propagation along a long UHVDC transmission line surrounded by space charges is analyzed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.