Abstract
In this paper, new time–frequency-based anomaly detection methodology is proposed for the condition monitoring of high-temperature superconducting (HTS) cable systems. The time–frequency-based anomaly detection methodology includes two indices, which are obtained via cross Wigner–Ville distribution and scattering parameter. For the validation of the proposed methodology, the methodology is applied to an ac 22.9-kV/50-MVA HTS cable system connected to the real power grid network. Furthermore, the changes in dielectric properties of the HTS cable system during the cooling process and the current imbalance failure are monitored. The proposed anomaly detection indices are shown to be able to detect the heat and the current imbalance caused by the malfunction of the joint box. For the application of the two validated indices, new anomaly detection procedure for HTS cable systems is also presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.