Abstract

The LiBr–H 2O single stage absorption water chiller, installed at the Municipal CHP plant of the city of Poznan, Poland was examined in order to find its energy performance. The 495 kW water chiller is used for CHP plant technological rooms air conditioning (e.g. control rooms, power supply rooms). The superheated steam ( p = 1.0 MPa, t = 250 °C) is the heat source for the generator and cooling water for the absorber and condenser is supplied from the existing cooling water installation. The chilled water temperature is set at 6 °C. On the basis of online temperature and media flow measurements, the system’s energy balance was created. Employing the first law of thermodynamics the energy balance equation was solved and used for the derivation of the chiller’s COP factor. The work’s main goal was to establish the influence of the chiller’s actual load on the energy efficiency of the system. The economic evaluation of cooling energy unit price was carried out on the basis of the measured chiller’s COP factor.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.