In a traditional indirect dry cooling system, the heat exchanger bundles are circularly arranged around the circumference of a cooling tower, which suffers severely from ambient winds. In this paper, an elliptical arrangement of heat exchanger bundles, which surround a traditional circular cooling tower, is proposed to restrain the adverse impacts of ambient winds. Elliptically arranged heat exchanger bundles with four different minor to major axis ratios were investigated on the condition that the total heat transfer area is the same as the traditional indirect dry cooling system. The flow and temperature fields of cooling air in the absence/presence of ambient winds were obtained. The mass flow rate, heat rejection and outlet water temperature of the alternative indirect dry cooling systems were calculated and analyzed. The results show that the elliptically arranged heat exchanger with a small ratio of minor to major axis is superior in thermo-flow performance at high wind speed. It is recommended that indirect dry cooling system incorporating elliptically arranged heat exchanger bundles be applied in regions with strong prevailing winds to achieve better thermo-flow performance.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.