Abstract

In order to study the influence of harmonic current loss characteristics on the thermal effect of UHV dry smoothing reactor, the author proposes a thermal effect monitoring system under the loss mechanism of dry smoothing reactor. By adding the electromagnetic loss density to the temperature field as a heat source, the electromagnetic-thermal multiphysics mapping relationship is established, the convective heat transfer process is more accurately simulated, and the temperature rise calculation is realized. Finally, the temperature rise test of the dry-type smoothing reactor is carried out. Experimental results show that using the calculation method considering the characteristics of harmonic loss, the maximum error between the calculated value and the experimental value is 9.1%, the average error is 4.34%, and the temperature rise distribution law is in good agreement. The system meets the requirements of engineering precision and provides the corresponding theoretical basis for engineering designers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.