Abstract

The heat transfer and the pressure drop characteristics of turbulent flow of air through rectangular and square ducts with internal transverse rib turbulators on two opposite surfaces of the ducts and with wire-coil inserts have been studied experimentally. Circular duct has also been used. The transverse ribs in combination with wire-coil inserts have been found to perform better than either ribs or wire-coil inserts acting alone. The flow friction and thermal characteristics are governed by duct aspect ratio, coil helix angle and wire diameter of the coil, rib height and rib spacing, Reynolds number and Prandtl number. Correlations developed for friction factor and Nusselt number have predicted the experimental data satisfactorily. It has been found that on the basis of constant pumping power, up to 35% heat duty increase occurs for the combined ribs and wire-coil inserts case compared to the individual ribs and wire-coil inserts cases in the measured experimental parameters space. On the constant heat duty basis, the pumping power has been reduced up to 20% for the combined enhancement geometry than the individual enhancement geometries.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.