Abstract

Due to their energy saving and thermal comfort, radiant cooling (RAC) systems have attracted growing interests all around the world in recent years. However, condensation has been troubling the wide application of RAC systems. In this paper, being analogous to the sky radiative cooling, a method of infrared (IR) transparent cover preventing condensation on the RAC surface is proposed. The feasibility of this method is analyzed theoretically by modeling. The key factors affecting the anti-condensation performance are studied in detail, including flow regimes in the interlayer, mean IR radiative properties of transparent covers and relative humidity of indoor air. It is shown that the RAC system equipped with an IR transparent cover could operate without condensation as long as the relative humidity is not more than 79.2%. The temperature of the RAC surface could be lowered to 7 °C when the relative humidity is less than 65%. The method could overcome the limitation of the dew point temperature on the cooling capacity partly. It is conducive to the application of RAC systems in hot and humid environments.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.