Abstract

A theoretical model of an ejector was proposed for a transcritical carbon dioxide ejector-expansion refrigeration system capable of predicting the mass flow rates of both primary and secondary flows. A non-equilibrium correlation in the energy-conservation equation was proposed and validated using 130 cases obtained from three different ejector configurations. The differences in the predicted primary mass flow rates between the cases with and without the correlation were insignificant when the liquid mass fraction at the nozzle throat xt was less than 0.65. However, the prediction error increases dramatically when the correlation was not used for xt > 0.65. The Mach number in the CO2 ejector is lower than 1.5 and the “double choking” phenomenon will not happen in the CO2 ejector. Finally, a correlation was fitted for the primary flow pressure at the nozzle throat, which can be used to replace iterative solving in the model calculation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.