Abstract

Absorption refrigeration can utilize low grade heat, but the application is limited by the huge system size and low energy efficiency. The mass transfer area of absorber occupies more than 50% of the whole system. The improvement absorption effect of the absorber is significant to reduce the system size and improve the energy efficiency ratio. A method to enhance the mass transfer in an ammonia-water falling absorber by implementing ultrasonic oscillators is proposed in this paper. A mathematical model of the absorber with the installing of oscillator is established. The solution of the model shows that the total mass transfer coefficient and the ammonia absorbed rate are increased by 22.53% and 20.25%, respectively, when the sound intensity at the surface of oscillator is 20 W/m2. The enhancement effect increases with oscillation output power, the ammonia absorbed rate increases by 31.2% when the sound intensity at the surface of oscillator is 50 W/m2.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.